E1311A
Display mode:
Mechanical register display
Display format:
①XXXXX.X (5-digit integer + 1-digit decimal) (Default)
②XXXXXX.X(6-digit integer + 1-digit decimal) With check valve
E1311L
Display mode:
LCD
Display format:
①XXXXXX.X(6-digit integer + 1-digit decimal)(Default)
②XXXXX.XX(5-digit integer + 2-digit decimal)
③XXXXX.X (5-digit integer + 1-digit decimal)
Description
The two types of electricity meters are used to measure single phase two wire AC active energy. Utilizing SMT (Surface mounting technology) to manufacture, the meters completely accord with the international standard IEC62053-21.
Features
1. Active energy is measured bi-directionally and reverse electricity will be measured and counted into total electricity.
2. Reverse indicator light
3. Power indicator lights
4. Impulse indicator light will flicker to show working status when passive pulse outputs.
5. Two kinds of case shells available: Protection I or Protection II.
Optional Function
1. Dead battery display added (E1311L only)
2. 48-hour supercapacitor power cut display added (E1311L only)
3. Shell sealing utilizes ultrasonic welding instead of screw sealing.
Technical Data
Rate voltage | 110/220V , 120/240V |
Working voltage range | 0.8~1.2Un |
Rate Current | 5A/CT,5(60)A,10(100)A, or special required |
Frequency | 60Hz |
Connection mode | Direct type or CT type |
Display | mechanical step register or LCD |
Accuracy class | 1.0 |
Power consumption | < 2W/10VA |
Start current | 0.004Ib |
AC voltage withstand | 4000V/25mA for 60 sec |
Impulse Voltage | 6kV 1.2μs waveform |
IP grade | IP51 or IP54 |
Constant | 800~3200 imp/kWh |
Pulse output | Passive pulse, pulse width is 80+5 ms |
Executive standard | IEC61036,IEC62053-21,IEC62052-11 |
Work temperature | -30℃~70℃ |
Outline dimension LXMXH | 145x105x50.5mm (short terminal cover L1) 175x105x50.5mm (Long terminal cover L2) |
Weight | Approx 0.5kg |
Export countries | North America, Central America, Colombia, Ecuador, Peru, Taiwan, Brazil |
Wire connection
Outline dimension