D1411
Display mode:
LCD
Display format:
① XXXXXX.X(6-digit integer + 1-digit decimal)(Default)
②XXXXX.XX(5-digit integer + 2-digit decimal)
Description
This meter is designed to measure single phase three wire AC active energy and perfect for the secondary circuits with flat rate tariff or single phase electric equipment with narrow interior space. Made by SMT (Surface mounting technology) manufacturing process, the meter is in accordance with standard IEC62053-21.
Features
1. Active energy is measured bi-directionally and reverse electricity will be measured and counted into total electricity.
2. Power reverse indicator lights
3. Passive pulse output, conform to DIN43864 standard
4. Continuous data saving after power failure and lasting for more than 15 years.
5. Width of the meter is only 75mm. 35mm DIN-rail installation. Similar shape as 4P breaker.
Technical Data
Rate voltage | 110V,120V,220V,230V,240V |
Working voltage range | 0.8~1.2Un |
Rate Current | 5(60)A,10(100)A or other as required |
Frequency | 50Hz or 60Hz +10% |
Connection mode | Direct type |
Display | LCD |
Accuracy class | 1.0 |
Power consumption | < 1W/10VA |
Start current | 0.004Ib |
AC voltage withstand | 4000V/25mA for 60 sec |
Impulse Voltage | 6kV 1.2μs waveform |
Over current withstand | 30Imax for 0.01s |
IP grade | IP51 |
Constant | 800~3200 imp/kWh |
Pulse output | Passive pulse, pulse width is 80+5 ms |
Executive standard | DIN 43880,IEC62053-21,IEC62052-11 |
Outline dimension LXMXH | 102x82x65mm |
Weight | Approx 0.3kg |
Environment
Operating temperature | -25℃~55℃ |
Storage temperature | -40℃~80℃ |
Reference temperature | 23℃+2℃ |
Relative humidity | 0 to 95% , non-condensing |
Altitude | Up to 2500m |
Warm up time | 10s |
Mechanical Environment | M1 |
Electromagnetic Environment | E2 |
Degree of pollution | 2 |
Wire connection